crevis

GN-9231

CC-Link Network Adapter


제품비교 담기

도움이 필요하세요?

샘플요청 견적문의
썸네일이미지 원본

주요특징


Interface Specification, GN-9231 (CC-Link NETWORK ADAPTER)

Adapter Type

Slave node (CC-Link Version 1)
Max. Expansion Slot 63 slots
I/O Data Size System area : 16 points
RX/RY : 112 points(4staion occupied)
RWr/RWw : 16 points(4station occupied)
The number of device station 1 ~ 64
Baud Rate 156/625/2500/5000/10000Kbps
Interface Connector 5 Pin open connector
Other Serial Port RS232 for MODBUS/RTU, Touch Pannel or IOGuide
Serial Configuration (RS232) Node : 1 (Fixed)
Baud Rate : 115200 (Fixed)
Data bit : 8 (Fixed)
Parity bit : No parity (Fixed)
Stop bit : 1 (Fixed)
Indicator Node : 1 (Fixed)
Baud Rate : 115200 (Fixed)
Data bit : 8 (Fixed)
Parity bit : No parity (Fixed)
Stop bit : 1 (Fixed)
Indicator 5 LEDs
1 Green/Red, Module Status (MOD)
1 Green, Current Running Status (NET)
1 Green, Error Status (ERROR)
1 Green/Red Expansion I/O Module Statsus (IOS)
1 Green, Field Power Status
2 LEDs (each RJ45 Connector)
1 Green, Active
1 Yellow, Link
Module Location Starter module left side of G-Series system
Field Power Detection About 14Vdc
Station class Remote Device station
General Specification
UL System Power Supply voltage : 24Vdc nominal, Class2
System Power

Supply voltage : 24Vdc nominal
Supply voltage range : 15~30Vdc
Protection : Output current limit (Min. 1.5A)
Reverse polarity protection

Power Dissipation 70mA typical @ 24Vdc
Current for I/O Module 1.5A @ 5Vdc(When using in ‘60℃ ~ 70 ℃’ temperature environment,
the power dissipation is limited to 0.8A.)
Isolation System power to internal logic : Non-isolation
System power I/O driver : Isolation
UL System Power Supply voltage : 24Vdc nominal, Class2
Field Power Supply voltage : 24Vdc nominal(Max. 30Vdc)
* Field Power Range is different depending on IO Module series.
Refer to IO Module`s Specification.
Max. Current Field Power Contact DC 10A Max
Weight

<165g