crevis

GL-9087

PROFINET NETWORK ADAPTER


제품비교 담기

도움이 필요하세요?

샘플요청 견적문의
썸네일이미지 원본

주요특징


Interface Specification, GL-9087 (PROFINET NETWORK ADAPTER)

Adapter Type

Slave node (Profinet)
Protocol Profinet
Max. Expantsion Module 10 slots
Max. Input / Output Data Size

Max. Input 128 bytes / Output 128 bytes

Max Length Bus Line Up to 100m from Ethernet Hub/Switch with twisted CAT5 UTP/STP
Max. Nodes Limited by Profinet Specification.
Baud Rate 100Mbps, Auto-negotiation, Full duplex
Interface Connector RJ-45 socket * 2pcs
IP-Address Setup Via Master Device Software
IAP Mode

When DIP Switch 1 to 8 setting is 254 or 255

(Using only Internet Explorer / recommended version 11)

Indicator

4 LEDs

1 Green/Red, Module Status(MOD)

1 Green/Red, Network Status(NET)

1 Green/Red, Error Status(ERROR)

1 Green/Red Expansion I/O Module Status(IOS)

2 LEDs (each RJ45 Connector)

1 Yellow, Link/Active

1 Green, Not used
Module Location Starter module left side of G-Series system
General Specification
UL System Power Supply voltage : 24Vdc nominal, Class2
System Power

Supply voltage : 24Vdc nominal

Supply voltage range : 15~28.8Vdc

Protection : Reverse polarity protection
Power Dissipation 55mA typical @ 24Vdc
Current for I/O Module 1.0A @ 5Vdc
Isolation

System power to internal logic : Non-isolation
System power I/O driver : Isolation

UL Field Power Supply voltage : 24Vdc nominal, Class2
Field Power

Supply voltage : 24Vdc typical (Max. 30Vdc)

* Field Power Range is different depending on IO Module series.

Refer to IO Module`s Specification.
Max. Current Field Power Contact DC 8A Max
Wiring I/O Cable Max. 2.0㎟(AWG 14)
Torque 0.8Nm(7 lb-in)
Weight 76g
Module Size

22mm x 109mm x 70mm

Environment Condition Refer to ‘1. Environment Specification’
Pin No Signal Description
1 System Power, 24V
2

System Power, Ground

3 F.G
4 Field Power, Ground
5

Field Power, 24V