주요특징
M9222 (Profibus NETWORK ADAPTER) | |
Repeater Control Signal |
RS-485 Signal |
Freeze mode | Support |
Sync mode | Support |
Auto baudrate | Support |
Station type | Slave |
FMS support | Not supported |
Max. Network Node | 125 Nodes |
Max. Expansion Slot | 63 Slots |
I/O Data Size | Input : 244bytes / Output : 244bytes |
Indicators | 4 LEDs 1 Green/Red, Module Status (MOD) 1 Green, Receive Data (NET) 1 Green, Transmit Data (DIA) 1 Green/Red, Expansion I/O Module Status (IOS) |
Communication Rate | 9.6K ~ 12M (1.2Km~100m) |
Communication Speed | 9.6 ~ 12000 Kbps (Auto baudrate selection) |
Bus Connection | 9 Pin D-Sub Connector |
Module Location | Starter module left side of M-Series system |
General specification (Supplied by M7001) | |
UL System Power | Supply voltage : 24Vdc nominal, Class 2 |
System Power | Supply voltage : 24Vdc nominal Supply voltage range : 15~28.8Vdc Protection : Output current limit, Reverse polarity protection |
Power Dissipation | 80mA typical @ 24Vdc |
Current for I/O Module | 2.0A @ 5Vdc (If except for NA, current for I/O module is about 1.5A) |
Isolation | System power to internal logic : Non-isolation System power I/O driver : Isolation |
UL Field Power | Supply voltage : 24Vdc nominal, Class 2 |
Field Power | Supply voltage : 24Vdc typical (Max. 28.8Vdc) * Field Power Range is different depending on IO Module series. Refer to IO Module`s Specification. |
Max. Current Field Power Contact | DC 10A Max |
Single Wire | 0.205㎟ - 1.3㎟ (24-16 AWG) |
Torque | 0.8Nm(7 lb-in) |
Weight | 179g |
Module Size | 54mm x 110mm x 75mm |