주요특징
GL-9031 (CC-Link NETWORK ADAPTER, Light) Communication Interface Specification |
||
Adapter Type | Slave node (CC-Link Version 1) | |
Max. Expansion Slot | 12 Slots | |
I/O Data Size | System area : 16 points RX/RY : 112 points(4staion occupied) RWr/RWw : 16 points(4station occupied) |
|
The number of device station | 1 ~ 64 | |
Baud Rate | 156/625/2500/5000/10000Kbps | |
Interface Connector | 5 Pin open connector | |
Indicator | 4 LED 1 Green/Red, Module Status (MOD) 1 Green, Current Running Status (RUN) 1 Green, Error Status (ERR) 1 Green/Red Expansion I/O Module Statsus (IOS) |
|
Module Location | Starter module left side of G-bus system | |
Station class | Remote Device station | |
General Specification | ||
UL System Power | Supply voltage : 24Vdc nominal, Class2 | |
System Power |
Supply voltage : 24Vdc nominal |
|
Power Dissipation | 35mA typical @ 24Vdc | |
Current for I/O Module | 1.0A @ 5Vdc | |
Isolation | System power to internal logic : Non-Isolation System power I/O driver : Isolation |
|
UL System Power | Supply voltage : 24Vdc nominal, Class2 | |
Field Power | Supply voltage : 24Vdc typical (Max. 28.8Vdc) * Field Power Range is different depending on IO Module series. Refer to IO Module’s Specification. |
|
Max. Current Field Power Contact | DC 8A Max | |
Wiring | I/O Cable Max. 2.0mm2(AWG 14) | |
Torque | 0.8Nm(7 lb-in) | |
Weight | 71g | |
Module Size | 22mm x 109mm x 70mm |